How do you leak-test installed HEPA filters in a cleanroom, how often, and what are the acceptance criteria?

For FDA, one probe reading of 0.01% of the upstream concentration is a leak: replace the filter or repair a limited area, then retest. Scan the whole face and frame in place, the photometer probe about one to two inches away sampling at least one cubic foot a minute, with PAO or DOP. EU GMP Annex 1 asks for it at qualification and each requalification: at most every 6 months for grades A and B, 12 for C and D.Checked against its sources on 25 November 2026. How these answers are made

1HEPA filter integrity test acceptance criteria.

A HEPA filter integrity test, or leak test, checks an installed filter, its frame and its seal for leaks. EU GMP Annex 1 lists “Installed filter system leakage and integrity testing” in cleanroom qualification and an “Integrity test of final filters” in every requalification, but gives no number; it says “Reference for the qualification of the cleanrooms and clean air equipment can be found in the ISO 14644 series of standards.”1 The number in common use comes from FDA’s aseptic processing guidance: “A single probe reading equivalent to 0.01 percent of the upstream challenge would be considered as indicative of a significant leak and calls for replacement of the HEPA filter or, when appropriate, repair in a limited area.”2

Table 1. The leak test as FDA’s 2004 aseptic processing guidance describes it, section IV.D.2.2
ParameterWhat FDA’s guidance asksWhat it means in practice
AcceptanceNo single probe reading of 0.01% of the upstream challenge or moreOne reading fails the filter
AerosolMeets specifications for physicochemical attributes such as viscosity; DOP and PAO are examplesEvaluating an alternative aerosol involves ensuring it does not promote microbial growth
Particle sizePolydispersed, light-scattering mean droplet diameter in the submicron range, with enough particles at about 0.3 µmThe mean is normally under 1 µm but above 0.3 µm
Upstream challengeIntroduced upstream, at a concentration appropriate for the accuracy of the photometerNo number is given; see the example below
ProbeIn place, a photometer probe on the downstream side sampling at least one cubic foot a minute28.3 liters a minute
DistanceAbout one to two inches from the filter face2.5 to 5.1 cm
CoverageThe entire filter face and frameLeaks occur at gaskets and frames as well as in the media
ResultDownstream leakage as a percent of the upstream challenge, fully documentedA photometer set to 100% on the upstream reads it directly
After repairA confirmatory retest in the area of any repairThen requalification, under Annex 1

The leak test is not the filter’s rating. “There is a major difference between filter leak testing and efficiency testing.” FDA defines a HEPA filter by its efficiency, retaining at least 99.97% of particles of 0.3 µm, measured with a monodispersed 0.3 µm aerosol and averaged over the whole filter; “Efficiency tests are not intended to test for filter leaks.”2 Japan’s aseptic guidance asks for the maker’s certificate of that efficiency and, separately, a leak test with an aerosol such as PAO.3 Annex 1 defines a HEPA filter only as one “specified in accordance with a relevant international standard”.1

WHO points to the ISO 14644 series for “Installed filter leakage”, and the series’ test method standard is ISO 14644-⁠3.4,5 It is sold, not public, so this page does not quote its figures. Its contents list two methods for the installed filter leakage scan, the “Aerosol photometer method” and the “Light-scattering airborne-particle counter (LSAPC) method”, each with its own probe size, scan rate and acceptance criteria; with a particle counter, a leak found in the scan is confirmed by stationary re-measuring.6 In the US the binding rule sits behind all of this: aseptic processing needs “An air supply filtered through high-efficiency particulate air filters under positive pressure” and “A system for maintaining any equipment used to control the aseptic conditions.”7

2How often HEPA filters must be leak tested.

Table 2. Leak-test frequency by regulator.
SourceAt installationRoutine intervalExtra tests
EU GMP Annex 1, 4.25 and 4.32;1 PIC/S and WHO the same8,9Part of cleanroom qualificationIn each requalification: at most 6 months for grades A and B, 12 months for C and DAfter remedial action, and after changes such as “change of final filters”
Annex 1, 8.671Depyrogenation tunnel filters “at least biannually”
FDA aseptic guidance, IV.D.22Yes, for gaskets, frames and media“For example, such testing should be performed twice a year for the aseptic processing room”Unacceptable air quality, renovations that disturb ceilings or walls, a media fill or sterility failure investigation; tunnel and oven filters included
FDA CP 7356.002A, item 2910A tunnel filter “normally undergoes integrity testing every 6 months”More often, depending on use and particle data outside the tunnel
Japan, MHLW aseptic guidance, 7.3.23Yes“at least once a year” in critical and direct support areas; twice or more where conditions are severeAfter events that may damage a filter, or when air quality deteriorates
WHO, non-sterile HVAC, 12.9 and 13.611Set from risk, the facility, the protection needed, performance and monitoringAfter every HEPA filter change

So a six-monthly test of the filters serving grades A and B meets the EU, PIC/S and WHO maximum, FDA’s example and Japan’s minimum at once. PIC/S reads the 4.32 list as a floor: “the requirements as listed in section 4.32 are the minimum requirements that should be included.”12 Annex 1 sets a maximum time interval, so count it from the last passing test, not from the start of a calendar half-year.

Annex 1 qualifies “unidirectional airflow units (UDAFs), RABS and isolators” on the same basis as cleanrooms, so the filters feeding a RABS or isolator are in the program.1 A changed filter is tested again: WHO’s guideline for non-sterile HVAC systems says a filter change “should be followed by installed filter leakage testing”.11

3HEPA filter leak test record template.

Keep one record per filter per test. A contractor’s certificate can carry the raw data, but FDA is plain about who answers for it: “Although contractors often provide these services, drug manufacturers are responsible for ensuring that equipment specifications, test methods, and acceptance criteria are defined, and that these essential certification activities are conducted satisfactorily.”2

Table 3. HEPA filter leak test record, field by field.
FieldWhat to recordSource
FilterFilter ID, room, grade, position on the ceiling plan, size, filter class and the maker’s efficiency certificateAnnex 1 glossary;1 MHLW 7.3.13
ReasonInstallation, periodic requalification, filter change, remedial action or investigationAnnex 1 4.25 and 4.32;1 FDA IV.D.22
Due dateDate of the last passing test and the maximum interval for the gradeAnnex 1 4.321
MethodProcedure reference and version, and the standard it followsAnnex 1 4.25;1 FDA IV.D.22
AerosolPAO, DOP or a justified alternative, its lot, and evidence it meets its specification and does not promote microbial growthFDA IV.D.22
InstrumentsAerosol generator and injection point; photometer ID and calibration dateFDA IV.D.22
UpstreamConcentration measured at this filter at the start and end of the scanFDA IV.D.22
ScanProbe flow (at least 28.3 L/min), distance (2.5 to 5.1 cm), whole face and frame coveredFDA IV.D.22
ReadingsHighest reading on the media and on the frame and seal, as % of upstream, and the position of any reading of 0.01% or moreFDA IV.D.22
VelocityReadings across the filter, 15 cm (6 inches) from the face, against the range set in the airflow pattern studiesFDA IV.D.22
Pressure dropPressure loss across the filter now, against its value at installationMHLW 7.3.23
OutcomePass, or leak: replaced or repaired, the area repaired, and the confirmatory retestFDA IV.D.22
DeviationDeviation number, the period since the last passing test, and the batches and monitoring results in that windowCipla warning letter13
ReviewTester and contractor, on-site reviewer, quality unit approval, next due dateFDA IV.D.2;2 CP 7356.002A, item 11910

4How it runs in Seal.

In Seal’s maintenance records, each filter’s leak test is a plan defined against the asset or component, with its trigger, procedure and post-service checks together, so the technician sees before starting what the reviewer will need. Calendar dates can drive the generated work, and a deferred test keeps its original due date, reason, risk assessment, authorization and revised date. A contractor’s access can be limited to their scope: which records they read, which evidence they submit, and which decisions stay with operations or quality. Each reading is a record in its own right, with its value, recorder and time. After a repair, a passing reading contributes evidence; it does not approve the repair, and return to service stays a separate, authorized decision.

When a filter fails, the contamination control strategy connects the maintenance event to the risks and product-exposure windows that need assessment. In commissioning and qualification, a failed acceptance stays attached to its requirement, expected result and actual observation, and the retest creates new evidence without overwriting the original failure.

5Example: six filters and a leak at the gasket.

Invented for illustration. Exampladine injection is filled on a RABS line whose grade A zone is fed by six ceiling HEPA filters, H-⁠A01 to H-⁠A06, in a grade B room. The last passing test was on 13 May 2026, so the six-month maximum runs to 13 November; the contractor tests on 11 November, 182 days later. PAO is injected upstream. The calibrated photometer reads the upstream at each filter’s sample port at the start and end of its scan, and the site’s procedure computes penetration against the lower of the two, so a falling upstream cannot flatter the result. The photometer cannot read reliably below 0.001 µg/L (an invented figure: take yours from the maker’s manual and your calibration), so lower readings are recorded as below 0.001.

Table 4. Example. Line, filters and readings are invented for illustration.
FilterUpstream at start (µg/L)Upstream at end (µg/L)Highest reading (µg/L)WherePenetration (%)Result
H-⁠A0125.124.7Below 0.001MediaBelow 0.0040Pass
H-⁠A0224.824.5Below 0.001MediaBelow 0.0041Pass
H-⁠A0324.924.40.0012Media0.0049Pass
H-⁠A0424.623.90.0045Frame, north-east corner gasket0.0188Leak
H-⁠A0525.324.8Below 0.001MediaBelow 0.0040Pass
H-⁠A0625.024.60.0021Media, near the center0.0085Pass
H-⁠A04 retest24.223.8Below 0.001MediaBelow 0.0042Pass

The calculation. For H-⁠A04, 0.0045 ÷ 23.9 × 100 = 0.0188%, nearly twice the 0.01% criterion. Against the starting upstream of 24.6 it is 0.0183%: a leak either way. H-⁠A06 passes at 0.0085%, 85% of the criterion, so the report notes it for comparison at the next test.

Why the upstream concentration matters. At an upstream of 23.9 µg/L, a reading of exactly 0.01% is 0.00239 µg/L. Had the upstream fallen tenfold, to 2.39 µg/L, the same 0.01% would be 0.00024 µg/L. Below this photometer’s 0.001 µg/L floor, that leak would sit in the noise. The minimum upstream is the lowest reliable reading divided by 0.0001: here 0.001 ÷ 0.0001 = 10 µg/L. That is FDA’s point when it says a leak test without a sufficient upstream challenge “is ineffective for detecting leaks.”2

The fix. The leak is at the gasket, not in the media, so the filter is reseated in its housing and the whole face and frame are scanned again: below 0.0042%, a pass. Annex 1 asks that “Appropriate requalification consisting of at least the above tests should also be carried out following completion of remedial action”, so classification, airflow volume, pressure differences and air velocity are repeated before the line restarts.1

The impact. The leak could have started at any time in the 182 days since the last pass. A deviation reviews the grade A viable and total particle results under H-⁠A04, and the interventions there, for every batch filled in that window, the correlation FDA found missing at Cipla.13

6When a filter fails, and the edge cases.

  • Replace or repair. FDA allows repair “when appropriate” and only “in a limited area”, then a retest there.2 It does not define a limited area, so your procedure must.
  • Investigate, and look for patterns. A failure is a deviation. Cipla’s failures clustered in adjacent filters; its investigations pointed to gasket deterioration and late replacement, and FDA noted filters installed beyond the limit in the firm’s own procedure.13 Trend failures by room, age and position.
  • Hot zones. FDA lists the filters in depyrogenation tunnels and ovens among those to leak test, and “Where justified, alternate methods can be used to test HEPA filters in the hot zones of these tunnels and ovens.”2 Heat expansion of filter and housing “can compromise the integrity and functionality of the HEPA filters”.10 See depyrogenation validation.
  • A leak test is not enough. “HEPA filter leak testing alone is insufficient to monitor filter performance.” FDA asks for velocity uniformity across the filter and relative to its neighbors, and for replacement where velocity is no longer uniform.2 Nor does a leak test show airflow protection: that is what a smoke study is for.
  • After a bad result elsewhere. FDA suggests extra leak testing when air quality is unacceptable and in investigations of a media fill or sterility failure.2
  • Not the same test as a sterilizing filter’s. Annex 1’s definition of a filter integrity test covers “product, gas or HVAC filter”, but liquid and gas filters are tested by methods such as the bubble point; see PUPSIT.1

7What inspectors cite.

FDA’s program for sterile drug inspections gives its investigators these questions: “How often are HEPA filters integrity tested? What test method is used? What is done if leaks are found? If done by an outside firm, are results reviewed by on-site personnel including the quality unit?”10

“In late 2018, your firm experienced excessive and atypical High Efficiency Particulate Air (HEPA) filters failures in a short period. More than 45 filters failed due to side leakages and media failures. The filters were often adjacent in the same room. You failed to adequately investigate these filter integrity test failures”

Cipla Limited, warning letter 320-⁠20-⁠26, 25 February 2020. FDA added that “HEPA filter integrity is essential to ensure aseptic conditions”, and asked for a root cause analysis explaining “why numerous and clustered HEPA filter failures occurred in such a very short period.”13

“We observed particle board between the HEPA filter surfaces and housing, rust on HEPA filter frames”

Optikem International Inc., warning letter, 20 June 2024. Under unidirectional airflow, the letter also found: “Your firm failed to perform (b)(4) testing for each of the HEPA filters”, with velocities at the wall filters “inadequate and inconsistent across the (b)(4) panels”.14

“This conclusion is flawed as these activities do not provide an assessment of unidirectional airflow protection of the aseptic processing line and are not a substitute for smoke studies.”

Vitae Enim Vitae Scientific Inc., warning letter, 17 March 2022, after the firm proposed to rely on HEPA filter tests and gauge calibration instead of smoke studies.15

8Regional differences and what is changing.

  • EU, PIC/S and WHO share one text: Annex 1, in operation since 25 August 2023, and the same paragraph 4.32 in the PIC/S GMP Guide (PE 009-⁠18, September 2026) and WHO’s TRS 1044, Annex 2.1,8,9 PIC/S PI 058-⁠1, in force since 28 October 2026, adds that viable counts are “not explicitly required for requalification”.12
  • US. The 2004 aseptic guidance is still FDA’s final guidance, and CP 7356.002A is still on FDA’s list of drug compliance programs.16,17 Its 0.01% criterion and twice-yearly example are recommendations, not regulation; the regulation is 211.42(c)(10).7
  • Japan. The MHLW guidance, in the English version of its April 2011 revision on PMDA’s site, sets at least yearly testing for critical and direct support areas.3
  • ISO 14644-⁠3. The 2019 edition is current but under review; a new edition could change the method your protocol cites.5

AQuestions and answers

What is the difference between a HEPA filter leak test and an efficiency test?

The efficiency test rates the filter: the maker challenges it with a monodispersed aerosol of 0.3 µm particles and reads the average downstream over the whole surface, and a HEPA filter must retain at least 99.97%. The leak test is done on site, in place, by scanning the downstream face and frame with a polydispersed aerosol to find local leaks through the media, frame or seal. FDA says efficiency tests are not intended to find leaks, so a maker’s certificate does not replace the installation leak test.

Should PAO or DOP be used for a HEPA filter leak test?

Either can be. FDA names dioctyl phthalate (DOP) and poly-alpha-olefin (PAO) as examples of appropriate aerosols, provided the aerosol meets specifications for attributes such as viscosity, and Japan’s aseptic guidance gives PAO as its example. FDA adds that evaluating any alternative aerosol involves ensuring it does not promote microbial growth. Name the aerosol in the procedure and record its lot on each test.

Can a leaking HEPA filter be repaired instead of replaced?

Sometimes. FDA says a reading of 0.01% of the upstream challenge calls for replacement or, when appropriate, repair in a limited area, followed by a confirmatory retest in that area. It does not define a limited area, so your procedure must say how much repair is allowed and when the filter is replaced instead. Under Annex 1, the room is then requalified with at least the minimum requalification tests.

What upstream aerosol concentration does a HEPA leak test need?

No GMP text gives a number. FDA asks for an upstream concentration appropriate for the accuracy of the photometer, because a leak of 0.01% must still read above the instrument’s floor. Divide the lowest reading your photometer gives reliably by 0.0001 to find the minimum upstream; a floor of 0.001 µg/L needs at least 10 µg/L. Measure the upstream at each filter, at the start and end of its scan.

Does a replacement HEPA filter need a leak test before use?

Yes. FDA and Japan’s guidance both ask for a leak test at installation, WHO’s guideline for non-sterile HVAC systems says a HEPA filter change should be followed by installed filter leakage testing, and Annex 1 names the change of final filters among the changes that can call for requalification of the room. Assess the change through change control and keep the area out of use until the test and any requalification pass.

Who is responsible when a contractor tests the HEPA filters?

The manufacturer. FDA’s aseptic guidance says that although contractors often provide these services, the drug manufacturer must make sure the specifications, test methods and acceptance criteria are defined and the work is done satisfactorily. FDA investigators ask whether results from an outside firm are reviewed by on-site staff, including the quality unit.

References17 sources

References

  1. 1EudraLex Volume 4, Annex 1, Manufacture of Sterile Medicinal Products, paragraphs 4.23 to 4.25, 4.32 and 8.67, and the glossary, European Commission, 22 August 2022, in operation from 25 August 2023. https://health.ec.europa.eu/system/files/2022-08/20220825_gmp-an1_en_0.pdf (read 25 November 2026)
  2. 2Sterile Drug Products Produced by Aseptic Processing: Current Good Manufacturing Practice, guidance for industry, section IV.D.2 and glossary, FDA, September 2004. https://www.fda.gov/media/71026/download (read 25 November 2026)
  3. 3Guidance on the Manufacture of Sterile Pharmaceutical Products by Aseptic Processing, sections 7.3.1 and 7.3.2, MHLW office communication, totally revised April 2011, English version, PMDA. https://www.pmda.go.jp/files/000153543.pdf (read 25 November 2026)
  4. 4Guidelines on heating, ventilation and air-conditioning systems for non-sterile pharmaceutical products, Part 2: Interpretation, WHO Technical Report Series No. 1019, Annex 2, Table A2.3, World Health Organization, 2019. https://cdn.who.int/media/docs/default-source/medicines/norms-and-standards/guidelines/production/who-good-manufacturing-practices-for-heating-ventilation-and-air-conditioning-systems-for-non-sterile-pharmaceutical-products-(part-2)-interpretation-of-guidelines.pdf (read 25 November 2026)
  5. 5BS EN ISO 14644-⁠3:2019, Cleanrooms and associated controlled environments, Test methods, identical to ISO 14644-⁠3:2019, status current, under review, BSI, published 30 June 2020. https://knowledge.bsigroup.com/products/cleanrooms-and-associated-controlled-environments-test-methods (read 25 November 2026)
  6. 6ISO 14644-⁠3:2019, Cleanrooms and associated controlled environments, Part 3: Test methods, contents, Annex B.7, Installed filter system leakage test, published by DIN. https://www.din.de/de/mitwirken/normenausschuesse/nhrs/veroeffentlichungen/wdc-beuth:din21:313319523/toc-3106932/download (read 25 November 2026)
  7. 721 CFR 211.42, Design and construction features, paragraph (c)(10), eCFR. https://www.ecfr.gov/current/title-21/section-211.42 (read 25 November 2026)
  8. 8PIC/S Guide to Good Manufacturing Practice for Medicinal Products, Annexes, PE 009-⁠18, Annex 1 paragraph 4.32, PIC/S, 24 September 2026. https://picscheme.org/docview/11333 (read 25 November 2026)
  9. 9WHO good manufacturing practices for sterile pharmaceutical products, WHO Technical Report Series No. 1044, Annex 2, paragraph 4.32, World Health Organization, 2022. https://cdn.who.int/media/docs/default-source/medicines/norms-and-standards/guidelines/production/trs1044-annex-2-gmp-for-sterile-pharmaceutical-products.pdf (read 25 November 2026)
  10. 10Compliance Program 7356.002A, Sterile Drug Process Inspections, Part III and Attachment A, items 26, 29 and 119, FDA, implemented 11 September 2015. https://www.fda.gov/media/75174/download (read 25 November 2026)
  11. 11Guidelines on heating, ventilation and air-conditioning systems for non-sterile pharmaceutical products, WHO Technical Report Series No. 1010, Annex 8, sections 12.8, 12.9 and 13.6, World Health Organization, 2018. https://cdn.who.int/media/docs/default-source/medicines/norms-and-standards/guidelines/production/trs1010-annex8-who-gmp-heating-ventilation-airconditioning.pdf (read 25 November 2026)
  12. 12PIC/S PI 058-⁠1, Interpretation of the most important changes in the Annex 1 on the manufacture of sterile products (2022), answer to 4.32, PIC/S, 28 October 2026. https://picscheme.org/docview/11495 (read 25 November 2026)
  13. 13Cipla Limited, warning letter 320-⁠20-⁠26, MARCS-⁠CMS 597511, FDA, 25 February 2020. https://www.fda.gov/inspections-compliance-enforcement-and-criminal-investigations/warning-letters/cipla-limited-597511-02252020 (read 25 November 2026)
  14. 14Optikem International Inc., warning letter, MARCS-⁠CMS 680264, FDA, 20 June 2024. https://www.fda.gov/inspections-compliance-enforcement-and-criminal-investigations/warning-letters/optikem-international-inc-680264-06202024 (read 25 November 2026)
  15. 15Vitae Enim Vitae Scientific Inc., warning letter, MARCS-⁠CMS 620576, FDA, 17 March 2022. https://www.fda.gov/inspections-compliance-enforcement-and-criminal-investigations/warning-letters/vitae-enim-vitae-scientific-inc-620576-03172022 (read 25 November 2026)
  16. 16Sterile Drug Products Produced by Aseptic Processing, guidance document page, status Final, FDA, content current as of 4 May 2020. https://www.fda.gov/regulatory-information/search-fda-guidance-documents/sterile-drug-products-produced-aseptic-processing-current-good-manufacturing-practice (read 25 November 2026)